Application and Configuration Examples
Factory default communications Port - Settings for the drive
are:
– Baud Rate:
9600
– Data Bits:
8
– Parity:
None
– Stop Bits:
1
– Serial Port:
COM1
Refer to “RS-232 Communication Test” on page 11-8 for
troubleshooting instructions.
6. Select
R
ead Drive Parameters
from the Communications menu.
7. Verify the Drive Name and Address are correct for the drive that is
being addressed.
8. Choose
OK
to load the drive parameters.
9. If the message box appears that a motor must be selected, select
OK. The Drive Setup window is displayed with Motor Model
selection parameter active. The motor may be selected from the
drop down box. If this message box does not appear, the motor
displayed in the Motor Model box was previously selected.
10. Select or verify the correct motor model number from the drop
down Motor Model list.
11. If a message advises that the drive must be reset, choose
Yes
,
12. Select
Follower: Master
E
ncoder
as the Operation Mode for the
drive.
13. Choose
Close
from the Drive Setup window.
14. Choose the
Drive
P
arameter
command icon from the Drive win-
dow, and then select the
Follower
tab.
15. Enter an appropriate
G
ear Ratio
as the Follower Input. The
default Gear Ratio is 1:1 (motor encoder pulses:master pulses). If
a Gear Ratio of 3:1 is entered, the motor is moved 3 encoder
pulses for every incoming master pulse.
16. Choose
Close
to exit the Drive Parameters window.
17. Verify the Status indicator is green.
18. Select the
I/O
C
onfiguration
command icon from the Drive Win-
dow.
Note: A motor must be selected for the parameters to load.