Power Connections
7-7
AC Power Cabling
The 1398-DDM-005 and -005X, 1398-DDM-009 and -009X,
1398-DDM-019 and -019X drives require single phase, 100 to 240
VAC rms power with an input frequency of 47 - 63 Hz. “Power” on
page G-5 lists the output power characteristics of the drives. The AC
input supplies power to the motor. Alternatively, the drive may be
powered by an external DC power source. In either case, an external
power source must provide input power to the I/O.
TB1-3, TB1-4 and TB1-5 are the single phase AC input power
terminals for the 1398-DDM-005 and -005X, 1398-DDM-009 and
-009X, 1398-DDM-019 and -019X.
!
Intro
ATTENTION: The user is responsible for conforming
with all applicable local, national and international codes.
Wiring practices, grounding, disconnects and overcurrent
protection are of particular importance. Failure to observe
this precaution could result in severe bodily injury or loss
of life.
!
Intro
ATTENTION: High voltage may be present on the ter-
minals of the drive. Remove power and disconnect the
power cable before making or removing any connection.
!
Intro
ATTENTION: Do not tin (solder) the exposed leads on
cables. Solder contracts over time and may loosen the con-
nection.
Table 7.3:
TB1 - AC Power Terminals
Signal
Description
Terminal
L1
100 to 240 Volts AC Line 1 input power
TB1-3
L2/N
100 to 240 Volts AC Neutral
TB1-4
Safety (earth) ground
TB1-5
NOTE
:
Torque all terminal connections to 1.25 Nm (11.0 lb-in).