Connection diagram, Configuration, Preset controller connection diagram – Rockwell Automation 1398-DDM-xxx ULTRA 100 Series Drives Installation Manual User Manual
Page 121: Connection diagram configuration
Publication 1398-5.2 – PDF 1997
Application and Configuration Examples
8-7
3. Connect a Power cable from the motor to TB1 (terminals R, S, T
and
) on the drive.
4. Connect a jumper wire with a toggle switch between the following
pins:
• J1-20 (ENABLE) and J1-26 (I/O PWR)
• J1-32 (INPUT1) and J1-26 (I/O PWR)
• J1-33 (INPUT2) and J1-26 (I/O PWR)
• J1-34 (INPUT3) and J1-26 (I/O PWR)
• Connect a switch between J1-21 (FAULT RESET) and J1-26
(I/O PWR).
These connections provide manual control for enabling or disabling
the drive and resetting faults. The figure below shows the jumper,
including normally open toggle switches.
1. Connect an external 12 to 24 VDC power source for powering I/O
to J1-5 (I/O PWR) and J1-6 (I/O COM).
2. Connect the drive to a single phase 100-240 VAC, 50/60 Hz power
source.
Connection Diagram
Configuration
Carefully check all connections before entering these parameters.
Figure 8.2
Preset Controller Connection Diagram
J1
26 I/O PWR
20 ENABLE
21 FAULT
32 INPUT1
33 INPUT2
Close to ENABLE Drive
Close to RESET Fault
34 INPUT3
Close to Turn ON
Close to Turn ON
Close to Turn ON
DRIVE
L1 3
L2/N 4
Gnd 5
100-240 VAC
50/50 Hz
Single Phase
Power Source
J5
2 RCV
3 XMT
5 COM
XMT
RCV
COM
RESET
TB1
Phase R 6
Phase S 7
Phase T 8
Mtr Gnd 9
J2
Motor
Encoder
External I/O
12-24 VDC
Power Source
5 I/O PWR
6 I/O COM