Pmcu, Attributes, Physical – HP NonStop G-Series User Manual

Page 166: Temperature sensor, Actions, Pmcu physical temperature sensor

background image

PMCU

The power monitor and control unit (PMCU) controls and monitors the battery connection to the DC power distribution
buses. Along with the service processor, the PMCU diagnoses the condition of the batteries, fans, and power supplies
and regulates the voltage supplied to the fans.

Location in OSM Tree: System > Group > Module > PMCU

Slot Location: PMCUs are located in slots 21 and 22 of Nonstop S-series processor or I/O enclosures (appearance
side).

Example: PMCU (1.1.21)

Attributes

PMCU

Displayed in the Attributes tab and Attributes dialog box only if the value is something
other than OK.

Values

Service State

Physical

A code that identifies the generation of the component. Hardware revision codes are
used for tracking components.

Hardware Revision

Identifies the manufacturer of the component.

Manufacturer

The part number of the component that was assigned in manufacturing. Use part
numbers for identifying and ordering parts.

Part Number

Whether the component is powered on.

Values

Power State

A unique serial number that identifies the component. Track IDs are used for tracking
components.

Track ID

Temperature Sensor

The minimum acceptable air intake temperature is 5 degrees Celsius. If the
temperature falls below 5 degrees, an alarm is generated.

Normal Minimum Value

The current temperature, in degrees Celsius (°C), inside the enclosure of the module.

Current Value

The maximum acceptable air intake temperature is 50 degrees Celsius. If the
temperature rises above 50 degrees, an alarm is generated.

Normal Maximum Value

Actions

None.

166