Yokogawa DAQWORX User Manual
Page 80

2-50
IM WX103-01E
Turnng Transmsson Output ON and OFF Collectvely for Analog Output/PWM Output
1. From the Action menu, choose Transmt.
Transmission output on active channels on the AO and PWM channel tabs is
performed collectively (All ON).
2. From the Action menu, choose Transmt again.
Transmission output on all active channels on the AO and PWM channel tabs is held
at the values that were in use immediately before this operation was carried out (All
OFF).
Explanaton
Settng Output for AO Channels
[Transmit]:
Computed values resulting from values measured on the MX100 and
computation results set on the computation channels are converted to
analog voltages (-10.000 V-10.000 V) or analog current (0.000mA-20.000
mA) and output.
Note
The output range is -11.000-11.000V or 0.000-22.000 mA, but the span setting range is
-10.000-10.000V or 0.000-20.000 mA.
[User Output]: Output continuously or a specified number of times an analog voltage or
analog current values using a previously set pattern. Also, you can enter
an arbitrary setting for User (Manual) in the Run screen. The setting
ranges are -10.000-10.000 V (voltage), or 0.000-20.000 mA (current).
Settng up Output for PWM Channels
[Transmission Output]: Outputs a duty pulse waveform corresponding to the measurement
values from the MX100 and the computation results set on the
computation channel.
[User Output]: Output continuously or a specified number of times a pulse duty ratio
(0.000 to 100.000%) using a previously set pattern. Also, you can enter
an arbitrary setting for User (Manual) in the Run screen.
Pulse interval
Output width
DUTY ratio = Output width
Pulse interval X 100 [%]
Settng Patterns
You can edit patterns when not monitoring. Point setting values consist of the elapsed
time from pattern start and the output value. The elapsed time for the first point is fixed at
0 seconds. Up to thirty-two points can be defined. Up to two points can occupy a single
point in time.
Also, you can easily generate four types of patterns using the Generate Automatically
function.
User Output
You can set up to four user outputs. With pattern output collective operation buttons, you
can output, stop, or pause all user outputs at once.
Collective action buttons (output, stop, pause)
User Output Procedure
• Pattern
1. Click the Pattern tab in the User Output space.
2. Click the triangle button. The previously set pattern is output.
2.8 Analog/PWM Output Settngs