Wiring the emergency-stop switch
In many cases multiple controllers are used in a single system.
To provide an emergency-stop function for the entire system, the controller circuit is designed in such a way that
a single EMG switch is able to actuate an emergency stop in all connected controllers.
[Internal emergency-stop circuit]
(Note) The current consumption of the internal relay is 10 mA or less.
(Reference)
Cutoff voltage
Cutoff current
EMG switch on teaching pendant
30 VDC
3 A
PORT switch
24 VDC
0.1 A
[Example of recommended circuit]
(Note) To cut off the motor drive power supply in conformance with safety category 2, connect 24V to the EMG
terminal and a contactor or other contact device to the MPI/MPO terminals. (Refer to 4.2.3; rush current:
8 A.)
MPO
MPI
S1
S2
24V
N
EMG
PORT
switch
Teaching pendant
Relay
Motor
power
supply
ON
OFF
Input power supply
(C:
2 A max.)
(CF:
6 A max.)
24V
0V
N
EMG signal
Controller
power supply
RCP2 controller
RCP2 controller
S1
S2
CR
ON
OFF
MPI
MPO
24V
EMG
N
CR
CR
24V
0V
External EMG
reset switch
External EMG
circuit
EMG switch on
teaching pendant
PORT switch
Coil current:
0.1 A or less
(3 A)
(0.1 A)
Relay