1 basic specifications, 2 connection example, Basic specifications – IAI America RCP2-CF User Manual
Page 137: Connection example

117
9. Controlling Multiple Controllers via Serial Communication
This section explains the connection method to be used when multiple controllers are controlled using the PC or
PLC’s communication module as the host.
9.1 Basic
Specifications
Specification item Description
Maximum number of units that can be connected
16 units
Maximum cable length
100 m or less
Terminal resistor
220
Provide a communication path via bus connection and be sure to provide a terminal resistor at the end.
9.2 Connection
Example
Note: Do not connect the teaching pendant and PC at the same time.
If both are connected at the same time, a communication error (message level) will occur.
PC, etc.
Teaching pendant
Optional
Cable length: 5
PC software
Optional
RS232C cross cable
(Provided by the user)
Components:
SIO converter (with built-in terminal resistor)
FG
0V
24V
Input power
supply
Controller power
supply
Terminal resistor
R = 220
Controller link cable
ADRS switch: 0
Controller 1
ADRS switch: 1
Controller 2
ADRS switch: n-1
Controller n
E-Con connector (AMP 4-1473562-4: housing color green)
E-Con connector (AMP 3-1473562-4: housing color orange)
Junction (AMP 5-1473574-4)
Green Green
Green
(Note) External equipment communication
cable
used for connection to a PC, PLC, etc.