Operation with the standard controller – IAI America RCP2-CF User Manual

Page 102

background image

82

7.2.3

Operation Timings at PIO Pattern = “0: [Conventional]”


(Example)

100 mm is set as the target position under position No. 3, and home position has not
been established yet

[Operation with the standard controller]
























[Operation with the absolute-specification controller]




















Note: With the absolute-specification controller, the actuator will not move to the target position if the

set position is “other than 0.”

Make sure the PLC can recognize that the actuator is stopped at the home position.

Command position PC1

PC2

Start CSTR

Position complete PEND


Home return completion HEND

Completed position PM1

PM2

Actuator movement

Mechanical end

Home position

Stops after moving to
the 100-mm position.

Command position PC1

PC2

Start CSTR

Position complete PEND


Home return completion HEND

Actuator movement

Mechanical end

Stops at the home position.

(Does not move to the 100-mm position.)