20
4.1.3
Wiring the Power Supply/Emergency-Stop Switch
(1)
Wiring the power supply
To connect multiple controllers, provide a relay terminal block.
Use a power cable satisfying the following specifications:
Item Specification
Applicable wire length
Single wire:
1.0 / Stranded: 0.8 mm
2
, AWG size 18 (copper wire)
Stripped wire length
10 mm
Temperature rating of
insulating sheath
60
C or above
* Use a flathead screwdriver with a blade tip of approx. 2.6 mm to push in the wire.
Notes on wiring the absolute-specification controller
[1] When connecting a relay to the 24-V line, be sure to install it on the positive side of the 24-V power supply.
Keep the negative side of the 24-V power supply connected without cutting it off with a relay.
If a relay is installed on both the positive and negative sides, an ABS error may generate.
[2] Connect a surge killer to the relay contact.
Chattering of the relay may have negative effect on the controller.
Connect a surge killer to prevent malfunction.
Recommended product: Spark Killer by Okaya Electric
Industries
Model number:
CR-50500
Capacitance: 0.5
F 20%
Resistance: 50
(1/2W) 30%
24V
0V
FG
S1
S2
MPI
MPO
24V
N
EMG
Input power supply
24 VDC
(2 A max. per controller)
Surge killer
Relay
Do not install a relay on the negative side.
RCP2-
ABS
24V+
N
24VPS
AC