Honeywell INTELLIKNIGHT 5820XL User Manual
Page 96
IntelliKnight 5820XL Installation Manual
5-6
151209
5.4.2
Wiring 5815XL in Style 6 & 7 (Class A) Configuration
Figure 5-3 illustrates how to wire the SLC loop for Style 6 or Style 7 Class A
installations.
Note: Style 6 does not use short circuit isolator devices.
Note: No t-taps allowed on class A SLC loops.
Figure 5-3 Class A SLC Configuration.
Caution
For proper system supervision do not use looped wire under terminals marked SLC + and – of the SLC device
connectors. Break wire runs to provide supervision of connections.