4.12.4 Installing 4-Wire Smoke Detectors
Any compatible U.L. listed four-wire smoke detector can be used with the control
panel (see Appendix A for list of compatible smoke detectors). Figure 4-34 and Figure
4-35 illustrate how to connect a UL listed four-wire detector to the control panel.
4.12.4.1 Installing a Class B 4-Wire Smoke Detectors
Figure 4-36 illustrates how to install a 4-wire Class B smoke detector.
Conventions used for wiring 4-wire Class B loops:
1. Up to three Class B 4-wire smoke detector loops can be connected to the control
panel at once.
2. Each Class B loop input is paired with a unique power source as shown in Figure
3. Each loop gets smoke power from the even numbered Flexput circuit and the con-
tact input is connected to the odd numbered Flexput circuit.
Figure 4-36 Class B 4-Wire Smoke Detector Connections
Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is
used to refer to the circuit pair. For example, Figure 4-36 uses both Flexput circuit 5 and 6, so in
programming it would be referred to as point 5.
Air Products
PAM-2
Model 160150
Supervision
Module
UL Listed
EOL Resistor
Model 7628
ESL 449CT
Note:
Flexput circuit 5 and 6
used as an example.
Any Flexput point pairing
could be used.
Supervised
Power Limited