3-11
3.6.1.2 Current Draw Worksheet for SD SLC Devices
Use Table 3-3 to determine current requirements during alarm/battery standby
operation when SD SLC devices are installed. You can install up 127 SD devices per
loop (508 max per panel). Copy this section if additional space is required.
Table 3-3: Current Draw Worksheet for SD SLC Devices
Device
# of Devices
Current per Device
Standby
Current
Alarm
Current
For each device use this formula: This column X This column = Current per number of devices.
IntelliKnight 5820XL Fire Panel
(Current draw from battery)
1
Standby: 215 mA
215 mA
Alarm: 385 mA
385 mA
Addressable SLC Devices
SD500-AIM
(508 max.)
1
Standby/Alarm: .55 mA
mA
mA
SD500-MIM
mA
mA
SD500-PS
SD500-ARM
mA
mA
SD505-AHS
mA
mA
SD505-AIS
mA
mA
SD505-APS
mA
mA
SD500-ANM
(508 max.)
1
Aux. Pwr
Standby: 8 mA
mA
Alarm: 60 mA
mA
SLC
Standby/Alarm: .55 mA
mA
mA
SD500-SDM
(508 max.)
1
SLC
Standby/Alarm: .55 mA
mA
Aux. Pwr
Standby: 20 mA
mA
Alarm: 106 mA
mA
SD500-LED
(100 max.)
1
Aux. Pwr
Standby: 10 mA
mA
Alarm: 220 mA
mA
LED: 10 mA
mA
mA
SLC
Standby/Alarm: .55 mA
mA
mA
SLC Accessory Bases
SD505-6RB
(508 max.)
Standby/Alram: .082 mA
mA
mA
SD505-6SB
(508 max.)
Aux. Pwr
Standby: 1 mA
mA
Alarm: 32 mA
mA
SLC
Standby/Alarm .082 mA
mA
mA
SD505-DUCTR
(508 max.)
Aux. Pwr
Standby: 20 mA
2
mA
Alarm: 62 mA
2
mA
SLC
Standby/Alarm: .5 mA
mA
mA
SD505-DTS-K
(508 max.)
None, included with SD505-DUCTR worst case.
SD505-DUCT
(508 max.)
None, included with detector current.
SLC Isolator Devices
SD500-LIM
(1024 max.)
Standby/Alarm .092 mA
mA
mA
SD505-6IB
(508 max.)
Accessories Modules
5815XL SLC Expander
(3 max.)
Standby/Alarm: 55 mA
mA
mA
5860 Remote Fire Alarm Annun.
(8 max.)
Standby: 20 mA
mA
Alarm: 25 mA
mA
5824 Serial/Parallel Printer
Interface
(2 max.)
Standby/Alarm: 45 mA
mA
mA
5895XL IntelliKnight Power
Expander
(8 max.)
Standby/Alarm: 10 mA
mA
mA
5496 Intelligent Power Module
Standby/Alarm: 10 mA
mA
mA