5 zone accessory options, 2 add zone, 3 delete zone – Honeywell INTELLIKNIGHT 5820XL User Manual
Page 139: 5 zone accessory options -13, 2 add zone -13 7.4.3 delete zone -13, N 7.4.1.5
Programming
151209
7-13
7.4.1.5 Zone Accessory Options
This option applies to detectors that are used with Sounder bases and Relay bases.
Single / Multi-station cadence pattern
Fire Cadence:_ _ / CO Cadence:_ _ (choose from Patterns 00 to 23).
Note: The B200S Sounder bases is intended to be used along with the CO Cadence setting.
Local Zone (choose Y or N, for Yes or No).
7.4.2
Add Zone
To add a zone, follow these steps:
1. Enter the installer code.
2. Press
or
to display the main menu.
3. Select
for Program Menu.
4. Press
to enter zone menu.
5. Press
to add a zone.
A zone will be added. The system will assign the next available zone number.
Options for this zone can now be programmed through the Zone Edit sub-menu.
Up to 125 zones can be used.
7.4.3
Delete Zone
To delete a zone, follow these steps:
1. Enter the installer code.
2. Press
or
to display the main menu.
3. Select
for Program Menu.
4. Press
to enter zone menu.
5. Press
to delete a zone.
A warning screen will display. If you want to proceed with deleting the zone, select
Yes. To cancel, select No.
ENTER
ACK
ENTER
ACK