Programming

151209

7-13

7.4.1.5 Zone Accessory Options

This option applies to detectors that are used with Sounder bases and Relay bases.

Single / Multi-station cadence pattern

Fire Cadence:_ _ / CO Cadence:_ _ (choose from Patterns 00 to 23).

Note: The B200S Sounder bases is intended to be used along with the CO Cadence setting.

Local Zone (choose Y or N, for Yes or No).

7.4.2

Add Zone

To add a zone, follow these steps:

1. Enter the installer code.

2. Press

or

to display the main menu.

3. Select

for Program Menu.

4. Press

to enter zone menu.

5. Press

to add a zone.

A zone will be added. The system will assign the next available zone number.
Options for this zone can now be programmed through the Zone Edit sub-menu.
Up to 125 zones can be used.

7.4.3

Delete Zone

To delete a zone, follow these steps:

1. Enter the installer code.

2. Press

or

to display the main menu.

3. Select

for Program Menu.

4. Press

to enter zone menu.

5. Press

to delete a zone.

A warning screen will display. If you want to proceed with deleting the zone, select
Yes. To cancel, select No.