Addressing SD Devices
This section explains how to address SD detectors and modules.
5.8.1
SD505-APS, SD505-AHS, & SD505-AIS
The SD505-APS photoelectric smoke detector, SD505-AHS heat detector, and
SD505-AIS ionization smoke detector are easily addressed at the FACP. The Installer
Code is required to perform this task.
To address a SD505-APS, SD505-AHS, or SD505-AIS:
1. Connect a detector base temporarily to the programming terminals as shown in
Figure 5-7. (You can use the same base for each detector).
Figure 5-7 Temporary Connection of Detector Base to Panel for Addressing
2. Enter the Installer code, then press
.
3. Select
for Point Functions.
4. Select
for Set SLC Dev Addr.
5. Select “Yes” by pressing the
up arrow, then press
. (The panel will go into
trouble at this point. You can use the
key to stop the PZT. The trouble will
clear automatically when the panel re initializes when you finish programming).
6. When the wait message clears, the following options display:
for Read Address. Use to read (or check) a single detector’s address.
for Write Address. Use to program a single detector’s address.
for Seq. Programming. Use to program more than one detector in sequential
order.
7. If you are changing addresses, write the programmed address on the back of the
device.
8. To exit press
left arrow until fully exited.
SILENCE