Honeywell INTELLIKNIGHT 5820XL User Manual
Page 29
Before You Begin Installation
151209
3-5
Figure 3-1 Wire Routing Example
Battery cables from
under aluminum housing.
Maintain 1/4"
spacing between
battery cables
and input wiring.
Red
Black
To
AC Input
Route all low voltage
wiring through any
of these knockouts.
All circuits, except battery
cables and AC, are power limited.
Maintain at least 1/4" spacing
between power limited and
non-power limited circuits.
Separate high and low
voltage circuits.
To phone
lines
Fire alarm power-limited circuits are
installed using types FPL, FPLR, FPLP
or permitted substitute cables,
provided these power-limited cable
conductors extending beyond the
jacket are separated by a minimum of
0.25 in. (6.35 mm) or by a nonconductive
sleeve or nonconductive barrier from
all other conductors.