Honeywell INTELLIKNIGHT 5820XL User Manual
Page 36
IntelliKnight 5820XL Installation Manual
3-12
151209
1. Total does not include isolator devices or accessory bases.
2. If using 24 VDC aux power only. No standby or alarm current for battery calculation if using 24 VAC, 120 VAC or
240 VAC.
3. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is
removed during that time. However, during normal operation, door holders draw current and must be included in the
6.0A total current that can be drawn from the panel.
4. Use next size battery with capacity greater than required.
5865-4 LED Annunciator
(with reset and silence switches)
(8 max.)
Standby: 35 mA
mA
Alarm: 145 mA
mA
5865-3 LED Annunciator
Standby: 35 mA
mA
Alarm: 145 mA
mA
5880 LED I/O Module
Standby: 35 mA
mA
Alarm: 200 mA
mA
5883 Relay Interface
(32 max.)
Standby: 0 mA
mA
Alarm: 220 mA
(22 mA per relay)
mA
A
Total System Current
Auxiliary Devices
3
Refer to devices manual for current rating.
Alarm/Standby: mA
mA
mA
Alarm/Standby: mA
mA
mA
Alarm/Standby: mA
mA
mA
Alarm/Standby: mA
mA
mA
B
Auxiliary Devices Current
Alarm: mA
mA
Alarm: mA
mA
Alarm: mA
mA
Alarm: mA
mA
C
Notification Appliances Current
mA
D
Total current ratings of all devices in system (line A + line B + C)
mA
mA
E
Total current ratings converted to amperes (line D x .001):
A
A
F
Number of standby hours:
H
G
Multiply lines E and F.
Total standby AH
AH
H
Alarm sounding period in hours. (For example, 5 minutes = .0833 hours)
H
I
Multiply lines E and H.
Total alarm AH
AH
J
Add lines G and I.
4
Total ampere hours
required
AH
Device
# of Devices
Current per Device
Standby
Current
Alarm
Current