7 releasing operations, Releasing operations -17 – Honeywell INTELLIKNIGHT 5820XL User Manual
Page 191
System Operation
151209
8-17
8.7
Releasing Operations
This control panel supports two types of releasing, Double Interlock Zone, and Single
Interlock Zone. The Double Interlock Zone operation requires an interlock switch
input in the system, and the Single Interlock does not. An interlock switch is typically
a dry-contact pressure switch.
When a Single or Double Interlock Zone releasing is selected the system is will
automatically default the following system parameters:
Note: The defaults created can be modified through programming if desired.
•
Output Group 2 is created. Output Group 2 will be defaulted as an “Alarm” output
group for all releasing zones. NAC [34:001] is assigned to Output Group 2.
•
Output Group 3 is created. Output Group 3 will be defaulted as an “Pre-Alert” out-
put group for all releasing zones. NAC [34:002] is assigned to Output Group 3.
•
Output Group 4 is created. Output Group 4 will be defaulted as a “Release” output
group for all releasing zones. NAC circuit [34:003] is assigned to Output Group 4.
Note: The installer must define which input points will be used for detectors, manual release switches,
or interlock/pressure switches.
Figure 8-5 Wiring Configuration for Solenoid
Do not mix cross alarming zones with smoke verification zones. There must be at
least two automatic detection devices in each protected space. Spacing must be
reduced to 0.7 times the linear spacing in accordance with NFPA 72. See Section 7.4
Table 8-2: Approved Releasing Solenoids
Manufacturer
Part Number
Rating
Current
Freq
Asco
T8210A107
24 VDC
3A max
0 Hz
8210G207
24 VDC
3A max
0 Hz
Model 7641
Must Mounted
at the Solenoid