3 battery connection, Battery connection -3 – Honeywell INTELLIKNIGHT 5820XL User Manual
Page 43
Control Panel Installation
151209
4-3
4.3
Battery Connection
The control panel battery charge capacity is 7.0 to 35 AH. Use 12V batteries of the
same AH rating. Determine the correct AH rating as per your current load calculation
(see Section 3.6).
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to
increase the AH rating. It is recommended that you replace batteries every five years.
Figure 4-2 Battery Connection
To Control Panel
Red
Black
Battery Jumper
(P/N 140694)
Shipped With Panel
UL Recognized
UL Recognized
12V Battery
12V Battery