Honeywell INTELLIKNIGHT 5820XL User Manual
Page 53
Control Panel Installation
151209
4-13
Flush Mounting with an Electrical Box
The 5860 annunciator can be used with the following types of electrical boxes: 4S,
single-gang, and double-gang.
If an electrical box is used, the box must be 1-3/8” back from the face of the wall to
accommodate the annunciator. Studs used with an electrical box must be two by
fours (or larger).
Figure 4-12 Placement of Electrical Box for Flush Mounting
Flush Mounting Steps
1. Cut a hole in the sheet rock to the following dimensions: 8¼” W x 6-5/8” H. If an
electrical box is used, the box must be 1-3/8” back from face of wall to accommo-
date the annunciator (see Figure 4-12).
2. Remove knockout holes as needed for wires.
3. Fit the annunciator back box into the hole and stabilize with mounting wires. Angle
the mounting wires into the first hole past the sheet rock. Secure the wires behind
the screws as shown in Figure 4-13. When all four wires are in place, the back box
should fit snugly into the hole in the sheet rock.
Sheet rock
Sheet rock
Electrical Box
Annunciator
back box
1-3/8"
When flush-mounting using an
electrical box, the box must be
1-3/8" from face of wall.
Electrical box applications require
2 by 4 construction minimum.
studs
electrical
box
annunciator
back box
(outline)
wall
Examples of Electrical Box Use
Electrical Box Placement