Honeywell INTELLIKNIGHT 5820XL User Manual
Page 122
IntelliKnight 5820XL Installation Manual
6-20
151209
System
Options
Reporting
Accounts
Edit Acct.
For each account (1-4), select:
Edit Account #
*123456
Account # (6-
digit number,
identifies
account to
central station)
Section 7.7.1
Edit Format
*Contact ID
Reporting
Format (SIA,
S20, Contact ID)
Section 7.7.1
Report Alarms
Y (Yes)
*Yes
Section 7.7.1
N (No)
M (Must)
Rep. Alarm
Restore
Y (Yes)
*No
N (No)
M (Must)
Report Troubles,
Supervisories,
Enable/Disable
Y (Yes)
N (No)
M (Must)
Report Test
Y (Yes)
N (No)
M (Must)
Report Resets
Y (Yes)
N (No)
M (Must)
Switch attempts
01 - 05
*5
Section 7.7.1
Edit Phone #1
up to 40 digits
blank
Section 7.7.1
Auto Test Time
Set the Hour
*02:00 AM
Section 7.7.1.2
Set the Minutes
Select AM/PM
Phone Lines
Select Phone
Line
For each phone line (1 & 2), select:
Dialing Prefix
Up to 9 digits
none
Section 7.7.2.1
# of Answer Rings Range: 00-15
06
Number of rings
before panel
answers a call
from a computer
Section 7.7.2.2
Select Dialing
Option
TT
TouchTone
Touch Tone
TT/PL
TouchTone
alternating with
pulse see
Section 7.7.2.3
PULSE
Pulse dialing
Rotary Pulse
Format
U = 60/40
*U
Section 7.7.2.4
E = 66/34
Line Monitor
Yes
*Yes
Section 7.7.2.5
No
Answering
Machine Bypass
Yes = enabled
*Y = Enabled Section 7.7.2.6
No = disabled
Menu
Options/Defaults
Comments