Honeywell INTELLIKNIGHT 5820XL User Manual
Page 135
Programming
151209
7-9
Mapping to Zone Events
Eight types of events can occur in zones. For each event type, you can activate up to
8 output groups or output group template, specifying a pattern for each. The following
is a list of all event types:
Note: Abbreviations in the parenthesizes are the characters that are displayed in programming (see
•
Manual Pull Alarm (MP)
•
Water Flow Alarm (WF)
•
Detector Alarm (DE). This applies to heat or smoke detectors.
•
Aux 1 and Aux 2 Alarm (A1 or A2). User-specified alarm types.
•
Pre-alarm (PR)
•
Supervisory (SU)
•
Trouble (TR)
•
Status Point (SP)
•
CO Alarm (CO)
•
CO Supervisory (SCO)
To map zone events to outputs:
1. From the Installer Main Menu, select
for Program Menu.
2. From the Program Menu, select
for Zone.
3. From the next menu, select
for Edit Zone.
4. Enter the zone number you wish to edit.
5. From the next menu, select
for Zone Outputs.
6. From the next screen, a list of 8 event types will display. Select the event type you
want to program. A screen similar to the one shown in Figure 7-3 will display.
Press .
7. Press the
or
key to toggle the group letter to either G = Group or T = output
group template depending on want you need for this zone. Press
.
ENTER
ACK
ENTER
ACK