2 event history, 2 event history -3 – Honeywell INTELLIKNIGHT 5820XL User Manual
Page 207
Testing and Troubleshooting
151209
10-3
condition is transmitted.
2) Notify facility personnel of a test so that alarm sounding devices are ignored during
the test period.
3) When necessary, activation of Notification Appliances can be prevented by the
DISABLE function
Testing:
1) Activate a input via an alarm initiating device and check that the correct outputs
activate (Notification Appliances sound/flash, relays activate, alarm LED lights).
Reset system. Repeat for each alarm initiating device.
2) Momentarily open the following circuits one at a time and check for a trouble
signal:
•
Notification Appliance (bell) Circuits.
•
Initiating devices
3) If new batteries were installed, wait 48 hours before completing this step.
Remove AC power, activate initiating device and check that:
•
The ALARM indicator lights.
•
All active Notification Appliances sound.
Measure battery voltage while the Notification Appliances are sounding. Replace any
battery with terminal voltage less than 85% of rating. Reapply AC power and RESET
system.
10.2.2 Event History
The event history can be useful for tracking or recalling a trouble condition.