IntelliKnight 5820XL Installation Manual
6-22
151209
System
Options
(cont.)
Misc. Options 1
Water Flow
Delay
0 - 90 Seconds
*30 sec
Water Flow delay is the
number of sec. before water
flow alarm is generated.
Section 7.7.4.1
Low AC Delay
0 - 30 hours
*3 hrs
Low AC Report
Delay. Section
7.7.4.2
DST
Y (Enabled)
*Enabled
Automatic Daylight Saving
Time enable or disable.
Section 7.7.4.3 and 7.7.6.3.
See also DST settings in Misc.
Option 3, below.
N (Disabled)
CLK
AM/PM
*AM/PM
System Clock Format (AM/PM
or military). Section 7.7.4.4
MIL
AC Freq:
50 Hz
Section 7.7.4.5
60 Hz
Neither
Misc. Options 2
SYNC Strbs w/
Sil
Y (Enabled)
*Disabled
Section 7.7.5.1
N (Disabled)
Auto Display
Oldest
Y (Enabled)
*Disabled
Section 7.7.5.2
N (Disabled)
Report By
Zone
*Zone
Section 7.7.5.3
Point
Misc. Options 3
Alarm
Verification
time
Enter time from 1
to 250 seconds
*60 Seconds
Section 7.7.6
Plex Door
Y (Enabled)
*Disabled
N (Disabled)
DST Start
Select week: 1st,
2nd, 3rd, 4th or
Last
Select month
Section 7.7.4.3
and 7.7.6.3. See
also DST
settings in Misc.
Options 1,
above.
DST End
Edit Banner
Internal
Message
Section 7.7.7
Custom
Message
Edit Line 1
Edit Line 2
JumpStart
AutoPrg
No
Section 7.8
Yes
Computer
Account
Computer
Account #
*5820
Section 7.9
Computer Access
Code
*0
Computer Phone
#
Up to 40 digits
Menu
Options/Defaults
Comments