1 current draw worksheet for sk slc devices, 1 current draw worksheet for sk slc devices -8, Able devices (table 3-2) – Honeywell INTELLIKNIGHT 5820XL User Manual
Page 32: S. use table 3-2 if inst
IntelliKnight 5820XL Installation Manual
3-8
151209
3.6.1.1 Current Draw Worksheet for SK SLC Devices
Use Table 3-2 to determine current requirements during alarm/battery standby
operation when SK SLC devices are installed. You can install up 99 SK detectors per
loop (396 max per panel) and 99 SK modules per loop (396 max per panel). Copy this
section if additional space is required.
Table 3-2: Current Draw Worksheet for SK SLC Devices
Device
# of Devices
Current per Device
Standby
Current
Alarm
Current
For each device use this formula: This column X This column = Current per number of
devices.
Fire Panel (battery current
draw)
1
Standby: 215 mA
215 mA
Alarm: 385 mA
385 mA
Addressable SLC Detectors
SK-Photo
(99 max/loop
& 396 max/
panel)
1
Standby: .30 mA
Alarm: 6.5 mA
mA
mA
SK-Photo-T
mA
mA
SK-Ion
mA
mA
SK-Heat
mA
mA
SK-Heat-HT
mA
mA
SK-Acclimate
mA
mA
SK-Heat-ROR
mA
mA
SK-Duct
5
(includes PhotoR)
mA
mA
SK-Beam (without integral test)
SLC
Standby/Alarm: 2 mA
Aux. Pwr
Standby: 2 mA
mA
Alarm: 8.5 mA
mA
SK-Beam-T
4
(with integral test)
SLC
Standby/Alarm: 2 mA
Aux. Pwr
Standby: 2 mA
mA
Alarm: 8.5 mA
mA
SK-FIRE-CO
SLC
Standby: .30mA
mA
Alarm: 7.2mA
mA