10 access codes, 10 access codes -47 – Honeywell INTELLIKNIGHT 5820XL User Manual
Page 172
IntelliKnight 5820XL Installation Manual
7-46
151209
7.10 Access Codes
Access codes provide the user access to the control panel functions. Each access
code can be customized for each user. This allows some users the ability to access
programming and other higher level panel functions, while other users may only need
access to lower level functions such as preforming fire drills, or acknowledging
trouble conditions.
Profile 1 is the profile that dictates what functions the Fire Fighter Key has access to.
Because this is the profile for a key the user name and the access code can not be
edited for this profile.
Profile 2 is the profile for the installer and is referred to as the “Installer Code”. This
profile’s user name and panel functions can not be edited.
Table 7-8 lists the panel functions that can be selected for each user profile.
To change an access code:
1. Enter the installer code.
Table 7-8: User Profile Selectable Panel Functions
Type of Function
Selectable
Functions
Panel Operations
System Reset
System Silence
System Event
Acknowledge
Fire Drill Key
Panel Menus
System Test
Fire Drill Menu
Indicator Test
Walk Test no Report
Walk Test with Report
Dialer Test
Clear History Buffer
Point Functions
Disable/Enable Point
Point Status
Set SLC Device Address
SLC Device Locator
SLC Mult-Device Locator
I/O Point Control
Event History
Set Time & Date
Printer Options
Event Logging
Print Event History
Print Detector Status
Print System Configuration
Reset Dialer
Program Menu
System Information
Upload/Download