3 electrical specification, Electrical specification -2 – Honeywell INTELLIKNIGHT 5820XL User Manual
Page 26
IntelliKnight 5820XL Installation Manual
3-2
151209
3.3
Electrical Specification
Table 3-1 list the terminal block on the 5820XL as well as a description of each
individual terminal and their respective electrical rating.
Table 3-1: Terminal Descriptions and Electrical Specifications
Terminal # and Label
Description
Rating
Earth Ground
Faults
Voltage
Current
1
L
AC input (hot)
120 VAC, 60 Hz 2.5 A
N/A
2
Earth ground
N/A
N/A
N/A
3
N
AC input (neutral)
120 VAC 60 Hz
2.5 A
N/A
4
X
*I/O 6
Flexput™ Circuits
24 VDC
3.0A notification and
auxiliary power circuits
0
5
O
100 mA for initiation
circuits
6
X
*I/O 5
Flexput™ Circuits
24 VDC
3.0A notification and
auxiliary power circuits
0
7
O
100 mA for initiation
circuits
8
X
*I/O 4
Flexput™ Circuits
24 VDC
3.0A notification and
auxiliary power circuits
0
9
O
100 mA for initiation
circuits
10
X
*I/O 3
Flexput™ Circuits
24 VDC
3.0A notification and
auxiliary power circuits
0
11
O
100 mA for initiation
circuits
12
X
*I/O 2
Flexput™ Circuits
24 VDC
3.0A notification and
auxiliary power circuits
0
13
O
100 mA for initiation
circuits
14
X
*I/O 1
Flexput™ Circuits
24 VDC
3.0A notification and
auxiliary power circuits
0
15
O
100 mA for initiation
circuits
16
B
SBUS
OUT
SBUS communication
5 VDC
100 mA
0
17
A
18
+
SBUS power
24 VDC
1.0 A
19
-
20
B
SBUS IN
Used for Class A installations
0
21
A
22
+
23
-
24
N.C.
RELAY 2
General Purpose Relay 2
24 VDC
2.5 A, resistive
N/A
25
C
26
N.O.
*
Regulated for NAC circuits, special application when used for releasing.