2 conventional input switch circuits, 1 class b inputs, 2 conventional input switch circuits -34 – Honeywell INTELLIKNIGHT 5820XL User Manual
Page 74: 1 class b inputs -34
IntelliKnight 5820XL Installation Manual
4-34
151209
4.12.2 Conventional Input Switch Circuits
This section of the manual explains how to install conventional initiating devices for
Class A (Style D) or Class B (Style B) configurations.
4.12.2.1 Class B Inputs
You can connect conventional Class B switches, such as waterflow switches and pull
stations, directly to the Flexput circuits of the control panel.
To install a Class B switch:
1. Wire the Class B switch as shown in Figure 4-32.
2. Configure the circuit through programming (see Section 7.6).
Figure 4-32 Class B Input Switches
UL Listed EOL
Model 7628
4.7 k
Supervised
Power Limited