beautypg.com

Honeywell INTELLIKNIGHT 5820XL User Manual

Page 33

background image

Before You Begin Installation

151209

3-9

Addressable SLC Modules

SK-Monitor

(99 max/loop

& 396 max/

panel)

1

Standby/Alarm: .375 mA

mA

mA

SK-Minimon

mA

mA

SK-Pull-SA

mA

mA

SK-Pull-DA

SK-Monitor-2

Standby/Alarm: .75 mA

mA

mA

SK-Mon-10

Standby/Alarm: 3.5 mA

mA

mA

SK-Control

SLC

Standby: 2.25 mA

mA

Alarm: 2.25 mA

mA

Aux Pwr

Standby: 1.7 mA

mA

Alarm: 7 mA

mA

SK-Control-6

SLC

Standby: 2.25 mA

mA

Alarm: 2.25 mA

Aux Pwr

Standby: 8 mA

mA

Alarm: 20 mA

mA

SK-Relay

Standby/Alarm: .255 mA

mA

mA

SK-Relay-6

Standby/Alarm: 1.45 mA

mA

mA

SK-Relaymon-2

Standby: 1.3 mA

mA

Alarm: 24 mA

mA

SK-Zone

Aux Pwr

Standby 12 mA

mA

Alarm 90 mA

mA

SLC

Standby/
Alarm .27 mA

mA

mA

SK-Zone-6

Aux Pwr

Standby 50 mA

mA

Alarm 270 mA

mA

SLC

Standby/Alarm 2 mA

mA

mA

B200SR Sounder Base

(99 max/loop

& 396 max/

panel)

Aux Pwr

Standby: .50 mA

mA

Alarm: 35 mA

mA

SLC

Standby .30 mA

mA

B200S Sounder Base

Aux

Standby .50 mA

mA

Alarm (high vol) 35 mA

mA

SLC

Standby .30 mA

mA

B224RB Relay Base

Standby/Alarm: 0.5 mA

mA

mA

RTS151/151 KEY

Alarm: 7.5 mA

mA

RA100Z

Alarm: 10 mA

mA

SK-Iso (Isolator Module)

(100 max/loop

&400 max/

panel)

Standby/Alarm: .45 mA

mA

mA

B224BI Isolator Base

Standby/Alarm: .5 mA

mA

mA

Accessories Modules

5815XL SLC Expander

(3 max.)

Standby/Alarm: 55 mA

mA

mA

5860 Remote Fire Alarm
Annunciator

(8 max.)

Standby: 20 mA

mA

Alarm: 25 mA

mA

5824 Serial/Parallel Printer
Interface Module

(2 max.)

Standby/Alarm: 45 mA

mA

mA

5496 Intelligent Power Module

(8 max.)

Standby/Alarm: 10 mA

mA

mA

5895XL IntelliKnight Power
Module

Standby/Alarm: 10 mA

mA

mA

Device

# of Devices

Current per Device

Standby

Current

Alarm

Current