4.12.5.3 Resettable Power
Resettable power is typically used to power beam detectors, flame detectors and
conventional 4-wire smoke detectors. For circuits selected as Resettable, 24-volt
power is always present at the terminals unless a system reset occurs. If a system
reset occurs, power is disconnected from the terminals for 30 seconds, then re-
applied.
4.13 On-Board Relays (Conventional)
The control panel has two built-in programmable relays and a built-in trouble relay. All
relays are Form C rated at 2.5 A @ 24 VDC.
Figure 4-39 Location of Conventional Relay Circuits
4.13.1 Trouble Relay
The control panel has a dedicated Form C trouble relay built into terminals 30-32. The
relay provides a normally open and a normally closed contact. The trouble relay will
deactivate under any trouble condition.
Note: The N.C. contact is the relay contact that is closed when the panel has power and there are no
trouble conditions.
4.13.2 Programmable Relays
The control panel has two Form C programmable relays built into terminals 24-29.
Each relay provides a normally open and a normally closed contact.
To install one or two programmable relays, follow these steps.
1. Wire Relay 1 and/or Relay 2 as needed for your application. See Figure 4-39 for
the location of the relay terminals.
2. Configure the relay through programming (see Section 7.6).