1 single interlock zone releasing, 1 single interlock zone releasing -18 – Honeywell INTELLIKNIGHT 5820XL User Manual
Page 192
IntelliKnight 5820XL Installation Manual
8-18
151209
for zone option programming.
8.7.1
Single Interlock Zone Releasing
A single interlock zone utilizes a minimum of two addressable detectors and a
designated manual release switch.
Conditions Required for an Pre-Alert Output Activation
If any single addressable detector is activated, the “Pre-Alert” output will activate.
This alerts the user that the initial stages required for a release condition are present.
(Also refer to Table 8-3.)
Conditions required for an General Alarm and Release Output Activation
If two or more addressable detectors, or a manual release switch activate, the
“Alarm” and the “Release” outputs will activate. (Also refer to Table 8-3.)
Important!
Only addressable detectors can be used. No conventional detectors can be used.
Each Single Interlock Zone input requires at least one manual release switch.
Table 8-3: Single Interlock Zone Operation
Inputs
Output Results
1st Addressable Detector
x
x
x
x
2nd Addressable Detector
x
x
x
x
Manual Release Station
x
x
x
x
Nor
m