4 wiring requirements for slc devices, 1 wiring 5815xl in style 4 (class b) configuration, Wiring requirements for slc devices -4 – Honeywell INTELLIKNIGHT 5820XL User Manual
Page 94: Ices to the 5815xl (see section 5.4)
IntelliKnight 5820XL Installation Manual
5-4
151209
5.4
Wiring Requirements for SLC Devices
The following information applies to all SLC devices. Refer to the section that
describes the type of device you are installing for details.
5.4.1
Wiring 5815XL in Style 4 (Class B) Configuration
No special wire is required for addressable loops. The wire can be untwisted,
unshielded, solid or stranded as long as it meets the National Electric Code 760-51
requirements for power limited fire protective signaling cables. Wire distances are
computed using copper wire.
Maximum wiring resistance is 40 ohms for SK devices and 50 ohms for SD devices.
Maximum loop length depends on the wire gauge. See Table 5-1 and Table 5-2.
Table 5-2 Maximum wiring distance for SD devices
Table 5-1 Maximum wiring distance for SK modules
Wire Gauge
Max. Distance for SK
22 AWG
1200 feet
18 AWG
3100 feet
16 AWG
4900 feet
14 AWG
7900 feet
12 AWG
10,000 feet
Wire Gauge
Max. Distance for SD
22 AWG
1500 feet
18 AWG
3900 feet
16 AWG
6200 feet
14 AWG
10,000 feet