Honeywell INTELLIKNIGHT 5820XL User Manual
Page 27
Before You Begin Installation
151209
3-3
27
N.C.
RELAY 1
General Purpose Relay 1
24 VDC
2.5 A, resistive
N/A
28
C
29
N.O.
30
N.C.
TROUBLE
Trouble Relay
24 VDC
2.5 A, resistive
N/A
31
C
32
N.O.
33
SC-
L1
SLC OUT
SLC terminals
32 VDC
150 mA
0
34
SC+
35
SC-
L2
SLC IN
Used for Class A installations
0
36
SC+
37
Ring
Phone Line 1 Telco Ring
N/A
0
38
Tip
Phone Line 1 Telco Tip
39
Ring
Phone Line 1 Premises Ring
40
Tip
Phone Line 1 Premises Tip
41
Ring
Phone Line 2 Telco Ring
N/A
0
42
Tip
Phone Line 2 Telco Tip
43
Ring
Phone Line 2 Premises Ring
44
Tip
Phone Line 2 Premises Tip
45
SC-
SLC Programming Terminal ( -
)
32 VDC
150 mA
0
46
SC+
SLC Programming Terminal ( +
)
32 VDC
150 mA
Table 3-1: Terminal Descriptions and Electrical Specifications
Terminal # and Label
Description
Rating
Earth Ground
Faults
Voltage
Current