Honeywell INTELLIKNIGHT 5820XL User Manual
Page 201
Reporting
151209
9-5
Point Events
Note:
Point events are reported only when "Report by Point" is selected. When SK
protocol devices are used,sensors 1–99 are reported as Pnt #s 1–99, and modules 1–99
are reported as Pnt #s 201-–299.
Manual pull switch alarm
Alarm
Point Event
pi Exp.
ID
FA
Pnt #
1
115
Exp.
ID
Pnt #
Manual release switch alarm
(Water Release Zone)
Alarm
Point Event
pi Exp.
ID
FA
Pnt #
1
110
Exp.
ID
Pnt #
Interlock switch alarm (Water
Release Zone)
Alarm
Point Event
pi Exp.
ID
FA
Pnt #
1
110
Exp.
ID
Pnt #
Detector alarm
Alarm
Point Event
pi Exp.
ID
FA
Pnt #
1
110
Exp.
ID
Pnt #
Point disabled
Disable
Point Event
pi Exp.
ID
FB
Pnt #
1
571
Exp.
ID
Pnt #
Manual pull switch alarm
restore
Restore
Point Event
pi Exp.
ID
FH
Pnt #
3
115
Exp.
ID
Pnt #
Manual release switch alarm
restore (Water Release Zone)
Restore
Point Event
pi Exp.
ID
FH
Pnt #
3
110
Exp.
ID
Pnt #
Interlock switch alarm restore
(Water Release Zone)
Restore
Point Event
pi Exp.
ID
FH
Pnt #
3
110
Exp.
ID
Pnt #
Detector alarm restore
Restore
Point Event
pi Exp.
ID
FH
Pnt #
3
110
Exp.
ID
Pnt #
Notification output trouble
restore
Trouble
Point Event
pi Exp.
ID
FJ
Pnt #
3
320
Exp.
ID
Pnt #
Manual pull switch trouble
restore
Trouble
Point Event
pi Exp.
ID
FJ
Pnt #
3
373
Exp.
ID
Pnt #
Manual release switch trouble
restore (Water Release Zone)
Trouble
Point Event
pi Exp.
ID
FJ
Pnt #
3
373
Exp.
ID
Pnt #
Interlock switch trouble restore
(Water Release Zone)
Trouble
Point Event
pi Exp.
ID
FJ
Pnt #
3
373
Exp.
ID
Pnt #
Detector trouble restore
Trouble
Point Event
pi Exp.
ID
FJ
Pnt #
3
373
Exp.
ID
Pnt #
Positive Alarm Sequence
acknowledge switch trouble
restore
Trouble
Point Event
pi Exp.
ID
FJ
Pnt #
3
373
Exp.
ID
Pnt #
Aux power trouble restore
Trouble
Point Event
pi Exp.
ID
FJ
Pnt #
3
320
Exp.
ID
Pnt #
Notification output trouble
Trouble
Point Event
pi Exp.
ID
FT
Pnt #
1
320
Exp.
ID
Pnt #
Manual pull switch trouble
Trouble
Point Event
pi Exp.
ID
FT
Pnt #
1
373
Exp.
ID
Pnt #
Manual release switch trouble
(Water Release Zone)
Trouble
Point Event
pi Exp.
ID
FT
Pnt #
1
373
Exp.
ID
Pnt #
Interlock switch trouble (Water
Release Zone)
Trouble
Point Event
pi Exp.
ID
FT
Pnt #
1
373
Exp.
ID
Pnt #
Detector trouble
Trouble
Point Event
pi Exp.
ID
FT
Pnt #
1
373
Exp.
ID
Pnt #
SIA Reporting Format
Contact ID Reporting Format
Event Description
Event
Family
Event Class
(System, Zone,
or Point)
Module
ID #
(if any)
SIA
Event
Code
Parameter
(if any)
Qualifier
Event
Code
Group
#
Contact
#