3 built-in troubleshooting and testing tools, 1 slc device locator, 3 built-in troubleshooting and testing tools -4 – Honeywell INTELLIKNIGHT 5820XL User Manual
Page 208: 1 slc device locator -4
IntelliKnight 5820XL Installation Manual
10-4
151209
10.3 Built-in Troubleshooting and Testing Tools
The fire control panel has several built-in testing and troubleshooting tools that can
be utilized to save time while testing and troubleshooting points and SLC devices.
10.3.1 SLC Device Locator
SLC device locator can be used to locate a device on a SLC loop.
Follow these steps to locate a particular SLC device:
1. Select
(Point
Functions) from the Main Menu.
2. Select
(SLC Dev Locator).
A message similar to the one shown in Figure 10-1 will display.
Figure 10-1 Shut Down Warning
3. Press the
or
arrow to toggle NO or YES then press
.
If NO is chosen you will exit back to the Point Function menu.
If Yes is chosen the system will cease normal operation leaving the premise
unprotected.
4. Select the SLC loop.
5. Enter the SLC address of the device you wish to locate.
The LED on the selected device will start flashing.
6. Press any key to exit SLC device locator function.
Note: Once you exit the system will resume normal operation.
ENTER
ACK