4 miscellaneous options 1, 1 water flow delay, 4 miscellaneous options 1 -39 – Honeywell INTELLIKNIGHT 5820XL User Manual
Page 164: 1 water flow delay -39, Section 7.7.4.1
IntelliKnight 5820XL Installation Manual
7-38
151209
7.7.4
Miscellaneous Options 1
Through this programming option you can set the water flow delay time, low AC
report delay, enable or disable automatic daylight savings time adjustment, clock
format, and AC clock frequency.
7.7.4.1 Water Flow Delay
You can program a delay of 0-90 seconds (zero means no delay) to be used in
conjunction with a water flow switch. The delay is system-wide. All water flow
switches on the system will use the same delay period.
To access the screen for programming water flow delay, follow these steps:
1. Enter the installer code.
2. Press
or
to display the main menu.
3. Select
for Program Menu.
4. Select
for System Options.
5. Select
for Miscellaneous Options 1.
A screen similar to the one shown in Figure 7-16 will display.
Figure 7-16 Water Flow Delay Programming Screen
6. Enter the number of seconds (0 to 90) to delay an a water flow switch alarm, then
press .
ENTER
ACK
Delay in seconds
before waterflow
alarm occurs.
(00 - 90)
ENTER
ACK