IntelliKnight 5820XL Installation Manual
7-24
151209
MAN REL
Latching
Manual release switch, typically a pull station.
Non Latching
ILOCK
Latching
Interlock release switch input.
Non Latching
CO Detect SW
CO Detector Switch
NOTIF
OUTPUT PT
Select Group
Output Point, a general use notification type. Use for driving
standard notification appliances.
AUX CONST
Use constant power for applications that require a constant
auxiliary power source. Power is always present at Constant
circuits.
AUX RESET
Use for auxiliary power, resettable applications. See Section
4.12.5.3 for a description of how this option operates.
AUX DOOR
Use for auxiliary power, door holder applications. For example,
if you were using an auxiliary power supply for door holders,
you would use this option. See Section 4.12.5.1 for a
description of how this option operates.
RELAY
OUTPUT PT
Select Group
Output Point, a general use relay type. Use for applications
requiring a relay, such as fan shutdown, elevator recall, and so
on.
AUX RESET
Select Group
Use for auxiliary power, resettable applications. See Section
4.12.5.3 for a description of how this option operates.
AUX DOOR
Select Group
Use for auxiliary power, door holder applications. For example,
if you were using an auxiliary power supply for door holders,
you would use this option. See Section 4.12.5.1 for a
description of how this option operates.
SLC LED
Select LED
No.
01 -80
Select Group
Table 7-5: Point Programming Options for 5815XL Modules
Type
Selection
Function
Latching
Option
Comments