Rosemount 5300 series – Emerson Process Management ROSEMOUNT 5300 User Manual
Page 98
Reference Manual
00809-0100-4530, Rev BA
July 2009
Rosemount 5300 Series
5-26
Analog Output (HART)
9. Configure the Analog Output
HART command: [2,1, 6].
Analog Output is not available for F
OUNDATION
Fieldbus.
Typically, the Primary Variable (PV) is configured to be Product Level,
Interface Level, or Volume. Other variables like Product Distance, Interface
Distance, Upper Product Thickness, etc. are available as well.
Specify the analog output range by setting the Lower Range Value (4 mA)
and the Upper Range Value (20 mA) to the desired values.
The Alarm Mode specifies the output state when a measurement error occurs.
See also “Analog Output (HART)” on page 5-9 for information on Analog
Output configuration.
Finish Configuration
Wizard
10. Finish the Configuration Wizard
This is the last window in the Configuration Wizard concluding the basic
configuration. The current configuration can be changed at any time by using
the Setup windows (General, Tank, Output etc., see “Using the Setup
Functions” on page 5-18).
The Setup windows contain further options not available in the configuration
wizard.
Click the Finish button and continue with the next step in the Guided Setup.