beautypg.com

Intrinsically safe output -12, Rosemount 5300 series – Emerson Process Management ROSEMOUNT 5300 User Manual

Page 70

background image

Reference Manual

00809-0100-4530, Rev BA

July 2009

Rosemount 5300 Series

4-12

Intrinsically Safe Output

When your power supply is intrinsically safe, wire the transmitter as shown in
Figure 4-10.

NOTE!
Make sure the instruments in the loop are installed in accordance with
intrinsically safe field wiring practices.

Figure 4-10. Wiring diagram for
intrinsically safe power supply
(Foundation Fieldbus).

IS parameters

(1)

Ui=30 V.

Ii=300 mA.

Pi=1.5 W (ATEX), 1.3 W (FM)

Ci=7.26 nF.

Li=0.

FISCO IS parameters

Ui=17.5 V.

Ii=380 mA.

Pi=5.32 W.

Ci=0.

Li=0.

Power
supply

Rosemount 5300 Series
Radar Transmitter

Approved IS Barrier

375 Field Communicator

PC

Fieldbus Modem

(1)

See Section B: Product Certifications for more information.