beautypg.com

Configure the ai block -39, Rosemount 5300 series, Reference manual – Emerson Process Management ROSEMOUNT 5300 User Manual

Page 111: Configure the ai block

background image

Reference Manual

00809-0100-4530, Rev BA
July 2009

5-39

Rosemount 5300 Series

CONFIGURE THE AI
BLOCK

A minimum of four parameters are required to configure the AI Block. The
parameters are described below with example configurations shown at the
end of this section.

CHANNEL

Select the channel that corresponds to the desired sensor measurement. The
Rosemount 5300 measures Level (channel 1), Distance (channel 2), Level
Rate (channel 3), Signal Strength (channel 4), Volume (channel 5), Internal
Temperature (channel 6), Upper Product Volume (channel 7), Lower Product
Volume (channel 8), Interface Distance (channel 9), Upper Product Thickness
(channel 10), Interface Level (channel 11), Interface Level Rate (channel 12),
Interface Signal Strength (channel 13), Signal Quality (channel 14),
Surface/Noise Margin (channel 15), and Vapor DC (channel 16).

L_TYPE

The L_TYPE parameter defines the relationship of the transmitter
measurement (Level, Distance, Level Rate, Signal Strength, Volume, and
Average Temperature) to the desired output of the AI Block. The relationship
can be direct or indirect root.

Direct
Select direct when the desired output will be the same as the transmitter
measurement (Level, Distance, Level Rate, Signal Strength, Volume, and
Internal Temperature).

Indirect
Select indirect when the desired output is a calculated measurement
based on the transmitter measurement (Level, Distance, Level Rate,
Signal Strength, Volume, and Internal Temperature). The relationship
between the transmitter measurement and the calculated measurement
will be linear.

AI Block

TB Channel Value Process Variable

Level

1

CHANNEL_RADAR_LEVEL

Ullage

2

CHANNEL_RADAR_ULLAGE

Level Rate

3

CHANNEL_RADAR_LEVELRATE

Signal Strength

4

CHANNEL_RADAR_SIGNAL_STRENGTH

Volume

5

CHANNEL_RADAR_VOLUME

Internal Temperature

6

CHANNEL_RADAR_INTERNAL_TEMPERATURE

Upper Product
Volume

7

CHANNEL_UPPER_PRODUCT_VOLUME

Lower Product
Volume

8

CHANNEL_LOWER_ PRODUCT_VOLUME

Interface Distance

9

CHANNEL_INTERFACE_ DISTANCE

Upper Product
Thickness

10

CHANNEL_UPPER_ PRODUCT_THICKNESS

Interface Level

11

CHANNEL_INTERFACE_LEVEL

Interface Level Rate

12

CHANNEL_INTERFACE_ LEVELRATE

Interface Signal
Strength

13

CHANNEL_INTERFACE_ SIGNALSTRENGTH

Signal Quality

14

CHANNEL_SIGNAL_QUALITY

Surface/Noise Margin

15

CHANNEL_ SURFACE_NOISE_MARGIN

Vapor DC

16

CHANNEL_VAPOR_DC