Rosemount 5300 Series

3-16

Figure 3-11. Tank connection
with loose flange (“plate
design”).

Threaded Connection

Figure 3-12. Threaded tank
connection.

Transmitter head

Gasket

Flange

Tank flange

Probe

Flange nut

Bolts

Nut

Transmitters delivered with Alloy probes featuring plate
design are mounted as described below:

1. Place a gasket on top of the tank flange.

2. Mount

(1)

the flange on the probe and tighten the flange

nut.

3. Mount

(1)

the transmitter head.

4. Lower the transmitter and probe with flange into the

tank.

5. Tighten the bolts.

6. Loosen the nut that connects the transmitter housing to

the probe slightly.

7. Rotate the transmitter housing so the cable

entries/display face the desired direction.

8. Tighten the nut.

(1) Flange and transmitter head are normally mounted at the factory.

Sealant on threads or
gasket (for BSP/G threads)

Nut

Tank connection

Probe

1. For tank connections with BSP/G threads, place

a gasket on top of the tank flange, or use a
sealant on the threads of the tank connection.

2. Lower the transmitter and probe into the tank.

3. Screw the adapter into the process connection.

4. Loosen the nut that connects the transmitter

housing to the probe slightly.

5. Rotate the transmitter housing so the cable

entries/display face the desired direction.

6. Tighten the nut.

NOTE!
For adapters with NPT threads, pressure-tight joints
require a sealant.