Reference Manual

00809-0100-4530, Rev BA
July 2009

5-11

Rosemount 5300 Series

BASIC CONFIGURATION
USING A 375 FIELD
COMMUNICATOR

This section describes how to configure the 5300 transmitter by using a 375
Field Communicator.

The menu tree with the various configuration parameters is shown in Figure
5-7 on page 5-12
. Section “Basic Configuration Parameters” on page 5-4
presents a description of the basic configuration parameters.

For information on all the capabilities, refer to the 375 Field Communicator
Product Manual (Document No. 00809-0100-4276).

Figure 5-6. The 375 Field
Communicator.

1. Check that the desired Measurement Units are selected.

2. Open the Process Variable menu and select Primary Variable. HART

command: [1,1]. Select the desired parameter.

3. Open the Basic Setup menu. HART command: [2, 1]. This menu

includes Probe, Tank Geometry, Environment, Volume, and Analog
Output settings.

4. Select Finish, Device Specific Setup to see if there is any additional

configuration that needs to be done.

5. Restart the transmitter. HART command: [3, 2, 1, 1].

See also “Guided Setup” on page 5-19 for further information on configuration
of the Rosemount 5300 transmitter.