Reference Manual

00809-0100-4530, Rev BA

July 2009

Rosemount 5300 Series

5-16

Installing the RRM
Software for
FOUNDATION Fieldbus

To install the Rosemount Radar Master for F

OUNDATION

Fieldbus

communication:

1. Start by installing the National Instruments Communication Manager

software. See National Instruments manual (Getting started with your
PCMCIA-FBUS and the NI-FBUS™ software
) for more information.

2. Insert the RRM installation CD into your CD-ROM drive.

3. If the installation program is not automatically started, choose Run from

the Windows Start bar.

4. Type D:\RRM\Setup.exe where D is the CD-ROM drive.

5. Follow the instructions on the screen.

6. Make sure that F

OUNDATION

Fieldbus is chosen as default protocol.

Getting Started

1. Before starting RRM make sure that appropriate settings are made with
the National Instruments Interface Configuration Utility:

If only Rosemount Radar Master is connected to the bus:
Device address=Fixed
Device Type=Link Master Device
Usage=NI-FBUS

If other host systems are connected to the bus:
Device address=Visitor
Device Type=Basic Device
Usage=NI-FBUS