Reference Manual

00809-0100-4530, Rev BA

July 2009

Rosemount 5300 Series

3-26

Mounting a Centering Disc on Rigid Single Probes

The mounting of a centering disc on a rigid single lead probe requires one
hole (8 mm probe) or two holes (13 mm probe) at certain distances from the
end of the lead. The drilling fixture included in your shipment should be used
to make the hole(s) according to Figure 3-14.

Table 3-9. Hole requirements on
probes for mounting a centering
disc.

Figure 3-14. Use drill template
for proper holes.

Rigid Single Lead probe (13 mm)

Probe

Minimum distance to hole

from probe end

Number of

holes

Hole diameter

8 mm

5 mm

1

3.5 mm

13 mm

7 mm (first hole)

2

3.5 mm

1. Mount the centering disc

at the end of the probe.

2. Fasten the disc by

inserting the split pins
through the bushings and
the probe.

3. Adjust distance by shifting

hole for split pin in lower
lockring.

4. Secure the split pin.

8 mm

13 mm

Probe

Drilling fixtures

Split pin

Split pin

Bushing

Lower
lockring

Washer