beautypg.com

Rosemount 5300 series – Emerson Process Management ROSEMOUNT 5300 User Manual

Page 237

background image

Reference Manual

00809-0100-4530, Rev BA
July 2009

B-15

Rosemount 5300 Series

Figure B-15. Approval Label
Canadian Standards Association
(CSA) Foundation Fieldbus
model

I6

Intrinsically Safe Ex ia.

Class I, Division 1, Groups A, B, C and D.

Temperature code T4.

F

OUNDATION

Fieldbus model: U

i

=30 Vdc, I

i

=300 mA, P

i

=1.3 W,

C

i

=0 nF, L

i

=0 H.

Control Drawing: 9240 030-937.

Ambient temperature limits: -50

°

C to + 60

°

C

Figure B-16. Approval Label
Canadian Standards Association
(CSA) FISCO model

IF

Intrinsically Safe Ex ia.

Class I, Division 1, Groups A, B, C and D.

Temperature code T4.

FISCO model: U

i

=17.5 Vdc, I

i

=380 mA, P

i

=5.32 W,

C

i

=0 nF, L

i

=0 H.

Control Drawing: 9240 030-937.

Ambient temperature limits: -50

°

C to + 60

°

C