Analog output status -41, Rosemount 5300 series, Reference manual – Emerson Process Management ROSEMOUNT 5300 User Manual

Page 171: Analog output status

background image

Reference Manual

00809-0100-4530, Rev BA
July 2009

7-41

Rosemount 5300 Series

Analog Output Status

Analog Output Status messages that may appear on the Integral Display, on
the 375 Handheld Communicator, or in RRM are shown in Table 7-10:

Table 7-10. Analog Output
status.

Message

Description

Action

Not connected

Analog output hardware is not
connected.

Alarm Mode

The analog output is in Alarm Mode.

Check Error and Warning Messages
to find the reason for the Alarm.

Saturated

The analog output signal value is
saturated, i.e. equal to the saturation
value.

No action needed.

Multidrop

The transmitter is in Multidrop Mode.
The analog output is fixed at 4 mA.

This is the normal setting when a
device is used in Multidrop
configuration.

Fixed Current mode

The analog output is in fixed current
mode.

This mode is used when calibrating
the Analog Output channel.

PV out of Limits

The Primary variable is out of range.

Check the Upper and Lower Range
Value

Span Too Small

The configured span is too small.

Check the Upper and Lower Range
Value.

Invalid Limits

The given Upper and Lower Sensor
Limits are invalid.

Check that the difference between the
Upper and Lower Sensor Limits is
greater than the Minimum Span.