In addition to the BLOCK_ERR and XD_ERROR parameters, more detailed
information on the measurement status can be obtained via
DIAGN_DEV_ALERT. Table F-17 lists the potential errors and the possible
corrective actions for the given values. The corrective actions are in order of
increasing system level compromises. The first step should always be to reset
the gauge and then if the error persists, try the steps in Table F-17. Start with
the first corrective action and then try the second.
Table F-17. Device Errors
Diagnostics
Bit Number
Value of
DIAGN_DEV_ALERT
Description
Corrective action
0
No alarm active
0
0x00000001
Reserved
1
0x00000002
FF card to gauge comm fault
Replace gauge
2
0x00000004
Level Measurement Failure
Verify device installation and configuration
3
0x00000008
Temperature Measurement
Failure
Check ambient temperature. If ambient
temperature ok replace the device.
4
0x00000010
Volume measurement failure
Check volume configuration
5
0x00000020
Database Error
Load default database to the device and
reconfigure the device
6
0x00000040
HW Error
Replace device
7
0x00000080
Microwave Unit Error
Replace device
8
0x00000100
Configuration Error
Load default database to the device and
reconfigure the device
9
0x00000200
SW Error
Replace device
10
0x00000400
Invalid Strap Table
Check the Strapping Table configuration
11
0x00000800
Internal Temp Warning
Check ambient temperature at installation site
12
0x00001000
Database Warning
Check the device configuration
13
0x00002000
HW Warning
Check device installation and configuration
14
0x00004000
Microwave Unit Warning
Check device installation and configuration
15
0x00008000
Configuration Warning
Check the device configuration
16
0x00010000
SW Warning
Check device installation and configuration
17
0x00020000
Simulation Mode
Use Simulation Method under advanced
configuration tool to get the device out of
Simulation Mode
18
0x00040000
Volume Range Warning
Verify Strapping Table
19
0x00080000
Software Write Protected
20
0x00100000
Vapor Compensation Not
Calibrated
21
0x00200000
Vapor DC Estimation Limited
22
0x00400000
Reference Reflector Not
Found
23
0x00800000
BaseLine too low
24
0x01000000
BaseLine too high
25
0x02000000
Gain control
26
0x04000000
Unsupported Combination of
Functions
27
0x08000000
28
0x10000000
29
0x20000000
Probe Missing
Check probe connection
30
0x40000000
Interface Measurement
Failure
Check interface measurement configuration
31
0x80000000
Hardware Write Protected