In addition to the BLOCK_ERR and XD_ERROR parameters, more detailed
information on the measurement status can be obtained via
DIAGN_DEV_ALERT. Table F-17 lists the potential errors and the possible
corrective actions for the given values. The corrective actions are in order of
increasing system level compromises. The first step should always be to reset
the gauge and then if the error persists, try the steps in Table F-17. Start with
the first corrective action and then try the second.

Table F-17. Device Errors
Diagnostics

Bit Number

Value of

DIAGN_DEV_ALERT

Description

Corrective action

0

No alarm active

0

0x00000001

Reserved

1

0x00000002

FF card to gauge comm fault

Replace gauge

2

0x00000004

Level Measurement Failure

Verify device installation and configuration

3

0x00000008

Temperature Measurement
Failure

Check ambient temperature. If ambient
temperature ok replace the device.

4

0x00000010

Volume measurement failure

Check volume configuration

5

0x00000020

Database Error

Load default database to the device and
reconfigure the device

6

0x00000040

HW Error

Replace device

7

0x00000080

Microwave Unit Error

Replace device

8

0x00000100

Configuration Error

Load default database to the device and
reconfigure the device

9

0x00000200

SW Error

Replace device

10

0x00000400

Invalid Strap Table

Check the Strapping Table configuration

11

0x00000800

Internal Temp Warning

Check ambient temperature at installation site

12

0x00001000

Database Warning

Check the device configuration

13

0x00002000

HW Warning

Check device installation and configuration

14

0x00004000

Microwave Unit Warning

Check device installation and configuration

15

0x00008000

Configuration Warning

Check the device configuration

16

0x00010000

SW Warning

Check device installation and configuration

17

0x00020000

Simulation Mode

Use Simulation Method under advanced
configuration tool to get the device out of
Simulation Mode

18

0x00040000

Volume Range Warning

Verify Strapping Table

19

0x00080000

Software Write Protected

20

0x00100000

Vapor Compensation Not
Calibrated

21

0x00200000

Vapor DC Estimation Limited

22

0x00400000

Reference Reflector Not
Found

23

0x00800000

BaseLine too low

24

0x01000000

BaseLine too high

25

0x02000000

Gain control

26

0x04000000

Unsupported Combination of
Functions

27

0x08000000

28

0x10000000

29

0x20000000

Probe Missing

Check probe connection

30

0x40000000

Interface Measurement
Failure

Check interface measurement configuration

31

0x80000000

Hardware Write Protected