Reference Manual
00809-0100-4530, Rev BA
July 2009
Rosemount 5300 Series
I-4
SAVE_CONFIG_NOW
61
Allows the user to optionally save all non-volatile information immediately.
SECURITY_IO
65
Status of security switch.
SELF_TEST
59
Instructs resource block to perform self-test. Tests are device specific.
SET_FSTATE
29
Allows the FAIL_SAFE condition to be manually initiated by selecting Set.
SHED_RCAS
26
Time duration at which to give up on computer writes to function block RCas locations.
Shed from RCas shall never happen when SHED_ROUT = 0
SHED_ROUT
27
Time duration at which to give up on computer writes to function block ROut locations.
Shed from ROut shall never happen when SHED_ROUT = 0
SIMULATE_IO
64
Status of simulate switch.
SIMULATE_STATE
66
The state of the simulate switch:
0 = Uninitialized
1 = Switch off, simulation not allowed
2 = Switch on, simulation not allowed (need to cycle jumper/switch)
3 = Switch on, simulation allowed
ST_REV
01
The revision level of the static data associated with the function block.
START_WITH_DEFAULTS
63
0 = Uninitialized
1 = do not power-up with NV defaults
2 = power-up with default node address
3 = power-up with default pd_tag and node address
4 = power-up with default data for the entire communications stack (no application data)
STRATEGY
03
The strategy field can be used to identify grouping of blocks.
SUMMARY_STATUS
56
An enumerated value of repair analysis.
TAG_DESC
02
The user description of the intended application of the block.
TEST_RW
08
Read/write test parameter - used only for conformance testing.
UPDATE_EVT
35
This alert is generated by any change to the static data.
WRITE_ALM
40
This alert is generated if the write lock parameter is cleared.
WRITE_LOCK
34
When hardware write protection is selected, WRITE_LOCK becomes an indicator of the
jumper setting and is unavailable for software write protection.
When software write lock is selected, and WRITE_LOCK is set, no writings from
anywhere else are allowed, except to clear WRITE_LOCK. Block input will continue to be
updated.
WRITE_PRI
39
Priority of the alarm generated by clearing the write lock.
XD_OPTION
44
Indicates which transducer block licensing options are enabled.
Parameter
Index
Number
Description