beautypg.com

Rosemount 5300 series, Reference manual – Emerson Process Management ROSEMOUNT 5300 User Manual

Page 302

background image

Reference Manual

00809-0100-4530, Rev BA

July 2009

Rosemount 5300 Series

I-4

SAVE_CONFIG_NOW

61

Allows the user to optionally save all non-volatile information immediately.

SECURITY_IO

65

Status of security switch.

SELF_TEST

59

Instructs resource block to perform self-test. Tests are device specific.

SET_FSTATE

29

Allows the FAIL_SAFE condition to be manually initiated by selecting Set.

SHED_RCAS

26

Time duration at which to give up on computer writes to function block RCas locations.
Shed from RCas shall never happen when SHED_ROUT = 0

SHED_ROUT

27

Time duration at which to give up on computer writes to function block ROut locations.
Shed from ROut shall never happen when SHED_ROUT = 0

SIMULATE_IO

64

Status of simulate switch.

SIMULATE_STATE

66

The state of the simulate switch:
0 = Uninitialized
1 = Switch off, simulation not allowed
2 = Switch on, simulation not allowed (need to cycle jumper/switch)
3 = Switch on, simulation allowed

ST_REV

01

The revision level of the static data associated with the function block.

START_WITH_DEFAULTS

63

0 = Uninitialized
1 = do not power-up with NV defaults
2 = power-up with default node address
3 = power-up with default pd_tag and node address
4 = power-up with default data for the entire communications stack (no application data)

STRATEGY

03

The strategy field can be used to identify grouping of blocks.

SUMMARY_STATUS

56

An enumerated value of repair analysis.

TAG_DESC

02

The user description of the intended application of the block.

TEST_RW

08

Read/write test parameter - used only for conformance testing.

UPDATE_EVT

35

This alert is generated by any change to the static data.

WRITE_ALM

40

This alert is generated if the write lock parameter is cleared.

WRITE_LOCK

34

When hardware write protection is selected, WRITE_LOCK becomes an indicator of the
jumper setting and is unavailable for software write protection.
When software write lock is selected, and WRITE_LOCK is set, no writings from
anywhere else are allowed, except to clear WRITE_LOCK. Block input will continue to be
updated.

WRITE_PRI

39

Priority of the alarm generated by clearing the write lock.

XD_OPTION

44

Indicates which transducer block licensing options are enabled.

Parameter

Index

Number

Description