beautypg.com

Rosemount 5300 series, Reference manual, Simulation – Emerson Process Management ROSEMOUNT 5300 User Manual

Page 309

background image

Reference Manual

00809-0100-4530, Rev BA
July 2009

J-3

Rosemount 5300 Series

SIMULATION

To support testing, you can either change the mode of the block to manual
and adjust the output value, or you can enable simulation through the
configuration tool and manually enter a value for the measurement value and
its status. In both cases, you must first set the ENABLE jumper on the field
device.

NOTE!
All fieldbus instruments have a simulation jumper. As a safety measure, the
jumper has to be reset every time there is a power interruption. This measure
is to prevent devices that went through simulation in the staging process from
being installed with simulation enabled.

With simulation enabled, the actual measurement value has no impact on the
OUT value or the status.

LO_PRI

29

None

The priority of the LO alarm.

LOW_CUT

17

%

If percentage value of transducer input fails below this, PV = 0.

MODE_BLK

05

None

The actual, target, permitted, and normal modes of the block.
Target: The mode to “go to”
Actual: The mode the “block is currently in”
Permitted: Allowed modes that target may take on
Normal: Most common mode for target

OUT

08

EU of OUT_SCALE

The block output value and status.

OUT_D

37

None

Discrete output to indicate a selected alarm condition.

OUT_SCALE

11

None

The high and low scale values, engineering units code, and number of digits to the
right of the decimal point associated with OUT.

PV

07

EU of XD_SCALE

The process variable used in block execution.

PV_FTIME

18

Seconds

The time constant of the first-order PV filter. It is the time required for a 63% change
in the IN value.

SIMULATE

09

None

A group of data that contains the current transducer value and status, the simulated
transducer value and status, and the enable/disable bit.

STRATEGY

03

None

The strategy field can be used to identify grouping of blocks. This data is not
checked or processed by the block.

ST_REV

01

None

The revision level of the static data associated with the function block. The revision
value will be incremented each time a static parameter value in the block is
changed.

TAG_DESC

02

None

The user description of the intended application of the block.

UPDATE_EVT

20

None

This alert is generated by any change to the static data.

VAR_INDEX

39

% of OUT Range

The average absolute error between the PV and its previous mean value over that
evaluation time defined by VAR_SCAN.

VAR_SCAN

40

Seconds

The time over which the VAR_INDEX is evaluated.

XD_SCALE

10

None

The high and low scale values, engineering units code, and number of digits to the
right of the decimal point associated with the channel input value.

Parameter

Index

Number

Units

Description