SIMULATION
To support testing, you can either change the mode of the block to manual
and adjust the output value, or you can enable simulation through the
configuration tool and manually enter a value for the measurement value and
its status. In both cases, you must first set the ENABLE jumper on the field
device.
NOTE!
All fieldbus instruments have a simulation jumper. As a safety measure, the
jumper has to be reset every time there is a power interruption. This measure
is to prevent devices that went through simulation in the staging process from
being installed with simulation enabled.
With simulation enabled, the actual measurement value has no impact on the
OUT value or the status.
LO_PRI
29
None
The priority of the LO alarm.
LOW_CUT
17
%
If percentage value of transducer input fails below this, PV = 0.
MODE_BLK
05
None
The actual, target, permitted, and normal modes of the block.
Target: The mode to “go to”
Actual: The mode the “block is currently in”
Permitted: Allowed modes that target may take on
Normal: Most common mode for target
OUT
08
EU of OUT_SCALE
The block output value and status.
OUT_D
37
None
Discrete output to indicate a selected alarm condition.
OUT_SCALE
11
None
The high and low scale values, engineering units code, and number of digits to the
right of the decimal point associated with OUT.
PV
07
EU of XD_SCALE
The process variable used in block execution.
PV_FTIME
18
Seconds
The time constant of the first-order PV filter. It is the time required for a 63% change
in the IN value.
SIMULATE
09
None
A group of data that contains the current transducer value and status, the simulated
transducer value and status, and the enable/disable bit.
STRATEGY
03
None
The strategy field can be used to identify grouping of blocks. This data is not
checked or processed by the block.
ST_REV
01
None
The revision level of the static data associated with the function block. The revision
value will be incremented each time a static parameter value in the block is
changed.
TAG_DESC
02
None
The user description of the intended application of the block.
UPDATE_EVT
20
None
This alert is generated by any change to the static data.
VAR_INDEX
39
% of OUT Range
The average absolute error between the PV and its previous mean value over that
evaluation time defined by VAR_SCAN.
VAR_SCAN
40
Seconds
The time over which the VAR_INDEX is evaluated.
XD_SCALE
10
None
The high and low scale values, engineering units code, and number of digits to the
right of the decimal point associated with the channel input value.
Parameter
Index
Number
Units
Description