Reference Manual

00809-0100-4530, Rev BA

July 2009

Rosemount 5300 Series

3-12

Recommended Mounting
Position for Liquids

Tank conditions are recommended to be carefully considered when finding
the appropriate mounting position for the transmitter. The transmitter should
be mounted so the influence of disturbing objects is reduced to a minimum.

In case of turbulence, the probe may need to be anchored to the bottom. See
“Anchoring“ on page 3-22 for more information.

Figure 3-8. Mounting Position

When mounting the transmitter the following guidelines should be considered:

Do not mount close to inlet pipes

Do not mount close to agitators. If the probe can move to within 30 cm
away from an agitator, a probe tie-down is recommended

If the probe tends to sway from the turbulent conditions in the tank, the
probe should be anchored to the tank bottom

Avoid mounting near heating coils

The nozzle should not extend into the tank

The probe should not come into contact with the nozzle or other objects
in the tank

Position the probe so it is subject to a minimum of lateral force

NOTE!
Violent fluid movements can cause forces that could break rigid probes.

Inlet pipe

Heating coils

Agitator