beautypg.com

Oundation, Rosemount 5300 series – Emerson Process Management ROSEMOUNT 5300 User Manual

Page 66

background image

Reference Manual

00809-0100-4530, Rev BA

July 2009

Rosemount 5300 Series

4-8

F

OUNDATION

FIELDBUS

Power Requirements

Terminals in the transmitter housing provide connections for signal cables.
The Rosemount 5300 transmitter is powered over F

OUNDATION

Fieldbus with

standard fielbus power supplies. The transmitter operates with the following
power supplies:

Connecting the
Transmitter

To connect the transmitter:

1. Make sure the power supply is switched off.

2. Remove the terminal block cover.

3. Pull the cable through the cable gland/conduit. Install wiring with a drip

loop. The bottom of the loop must be lower than the cable/conduit entry.

4. Connect wires according to Figure 4-9 for non-intrinsically safe power

supplies, and according to Figure 4-10 for intrinsically safe power
supplies.

5. Use the enclosed metal plug to seal any unused port.

6. Mount the cover and tighten the cable gland making sure the cover is

secure to meet explosion-proof requirements.

7. For ATEX, IECEx and NEPSI installations, lock the cover with the

Locking Screw

.

8. Connect the power supply.

NOTE!
Use PTFE tape or other sealant at the NPT threads in the Cable Entries.

Approval Type

Power Supply (Vdc)

IS

9 - 30

Explosion-Proof/Flameproof

16 - 32

None

9 - 32

FISCO; IS

9 - 17.5